 Rated capacity: 20MVA
 Rated voltage and tapping range: 35±3x2.5%/10.5kV
 Rated frequency: 50Hz
 Cooling method: AN
 phase: 3-phase
 Vector group:Yd11
 Insulation level
 HV wiring terminals: LI/AC 170/70
 LV wiring terminals: LI/AC 75/35
 
 Main property of the product:
 Impedance voltage: 10%, with stipulated tolerance in national standard
 No-load loss: 21kW
 No-load current: 0.3%
 Load loss: 85kW
 Total loss: 106kW
 Insulation and thermal resistance: H grade
 The temperature rise is designed at F level
 coil<100K
 Noise level: ≤62dB (1m)
 Partial discharge: ≤10pC
 
- 